Availability: | |
---|---|
Quantity: | |
A4465、A4466、A4467、A4468
Cat. No. | A4465 | A4466 | A4467 | A4468 | ||
Fig | 1 | 2 | 1 | 2 | ||
Unit spacing (H) mm | 160 | 146 | 160 | 146 | ||
Nominal diameter (D) mm | 280 | 280 | 280 | 280 | ||
Nominal Creepage Distance (mm) | 450 | 450 | 450 | 450 | ||
Rated E&M failing load (kN) | 100 | 100 | 120 | 120 | ||
Routine tensile load (kN) | 50 | 50 | 60 | 60 | ||
Coupling size | 16A/16B | 16A | 16A/16B | 16A | ||
Power frequency withstand voltage | Wet (kv) | 45 | 45 | 45 | 45 | |
Dry (kv) | 80 | 80 | 80 | 80 | ||
Dry lighting impulse withstand voltage (kV) | 120 | 120 | 120 | 120 | ||
Power frequency punctured voltage (kV) | 120 | 120 | 120 | 120 | ||
Radio-Interference- Voltage | Test Voltage to ground (kV) | 10 | 10 | 10 | 10 | |
Maximum RIV at 1MHz (µV) | 50 | 50 | 50 | 50 | ||
Weight (kg) | 8.40 | 8.40 | 8.40 | 8.40 | ||
Applicable standard: IEC GB AS BS |
Cat. No. | A4465 | A4466 | A4467 | A4468 | ||
Fig | 1 | 2 | 1 | 2 | ||
Unit spacing (H) mm | 160 | 146 | 160 | 146 | ||
Nominal diameter (D) mm | 280 | 280 | 280 | 280 | ||
Nominal Creepage Distance (mm) | 450 | 450 | 450 | 450 | ||
Rated E&M failing load (kN) | 100 | 100 | 120 | 120 | ||
Routine tensile load (kN) | 50 | 50 | 60 | 60 | ||
Coupling size | 16A/16B | 16A | 16A/16B | 16A | ||
Power frequency withstand voltage | Wet (kv) | 45 | 45 | 45 | 45 | |
Dry (kv) | 80 | 80 | 80 | 80 | ||
Dry lighting impulse withstand voltage (kV) | 120 | 120 | 120 | 120 | ||
Power frequency punctured voltage (kV) | 120 | 120 | 120 | 120 | ||
Radio-Interference- Voltage | Test Voltage to ground (kV) | 10 | 10 | 10 | 10 | |
Maximum RIV at 1MHz (µV) | 50 | 50 | 50 | 50 | ||
Weight (kg) | 8.40 | 8.40 | 8.40 | 8.40 | ||
Applicable standard: IEC GB AS BS |