P-11-A、P-22-A、P-33-A
The following pin insulators comply with the ANSI Standard.
The glaze colour of the insulators are brown, light gray, white, etc...
Fig | 1 | 2 | 3 | |||
Class AS | P-11-A | P-22-A | P-33-A | |||
Main Dimensions (mm) | H | 107 | 168 | 194 | ||
h | 40 | 63.5 | 63.5 | |||
D | 140 | 228 | 279 | |||
d | 76 | 113 | 113 | |||
R1 | 16 | 16 | 16 | |||
R2 | 13 | 13 | 13 | |||
Nominal Voltage(kV) | 11 | 22 | 33 | |||
Creepage Distance(mm) | 180 | 450 | 520 | |||
Minimum Flashover Voltage | Power-frequency (r.m.s) | Dry/kv | 60 | 80 | 120 | |
Wet/kv | 32 | 60 | 80 | |||
50% Critical Impulse (peak)/kV | 95 | 150 | 170 | |||
Power-Frequency Puncture Voltage /kV | 95 | 130 | 165 | |||
Cantilever Failing Load(kN) | 11 | 11 | 11 | |||
Weight (kg) | 1.3 | 4.6 | 8.9 |
The following pin insulators comply with the ANSI Standard.
The glaze colour of the insulators are brown, light gray, white, etc...
Fig | 1 | 2 | 3 | |||
Class AS | P-11-A | P-22-A | P-33-A | |||
Main Dimensions (mm) | H | 107 | 168 | 194 | ||
h | 40 | 63.5 | 63.5 | |||
D | 140 | 228 | 279 | |||
d | 76 | 113 | 113 | |||
R1 | 16 | 16 | 16 | |||
R2 | 13 | 13 | 13 | |||
Nominal Voltage(kV) | 11 | 22 | 33 | |||
Creepage Distance(mm) | 180 | 450 | 520 | |||
Minimum Flashover Voltage | Power-frequency (r.m.s) | Dry/kv | 60 | 80 | 120 | |
Wet/kv | 32 | 60 | 80 | |||
50% Critical Impulse (peak)/kV | 95 | 150 | 170 | |||
Power-Frequency Puncture Voltage /kV | 95 | 130 | 165 | |||
Cantilever Failing Load(kN) | 11 | 11 | 11 | |||
Weight (kg) | 1.3 | 4.6 | 8.9 |